标题:A Fully Controllable Power System - Concept for FACTS and HVDC Placement
查看原文 PDF 中文 PDF (下批处理) EasyResearch 阅读摘要:This paper puts forward the vision of fully decoupling market operations from security considerations through controllable power flows. In "A Fully Controllable Power System", power system security is no longer dependent on the location of the power injection points. In the ideal case, this leads to the elimination of redispatching costs, which amount to several million dollars per year in large systems. This paper determines the upper and lower bounds for the number of controllable lines and number of controllers to achieve this decoupling in any system. It further introduces the notion of the controllability vector CV, which expresses the effect of any controller on the AC line flows. Based on two alternative definitions for controllability, two controller placement algorithms to maximize controllability are presented and their results are compared.