统计学 > 应用
[提交于 2016年1月8日]
标题:Quaternion-Valued Single-Phase Model for Three-Phase Power Systems
查看原文 PDF 中文 PDF (下批处理) EasyResearch 阅读摘要:In this work, a quaternion-valued model is proposed in lieu of the Clarke's \alpha, \beta transformation to convert three-phase quantities to a hypercomplex single-phase signal. The concatenated signal can be used for harmonic distortion detection in three-phase power systems. In particular, the proposed model maps all the harmonic frequencies into frequencies in the quaternion domain, while the Clarke's transformation-based methods will fail to detect the zero sequence voltages. Based on the quaternion-valued model, the Fourier transform, the minimum variance distortionless response (MVDR) algorithm and the multiple signal classification (MUSIC) algorithm are presented as examples to detect harmonic distortion. Simulations are provided to demonstrate the potentials of this new modeling method.
提交历史
来自:Zhiwen Liu Prof.[v1] 2016年1月8日 星期五 00:00:00 UTC