标题:Security Constrained Unit Commitment with Corrective Transmission Switching
查看原文 PDF 中文 PDF (下批处理) EasyResearch 阅读摘要:Traditionally, power system operations use a static network to deliver power and meet demand optimally. Network topology reconfiguration through transmission switching (TS) has gained significant interest recently to reduce the operational cost of power system operations. However, implementation of TS also causes large disturbance in the network and as a result the use of corrective transmission switching (CTS) in response to power system contingencies is currently being researched extensively. This paper emphasizes the importance of CTS to accomplish flexible transmission in N-1 security-constrained unit commitment (SCUC) model. An N-1 SCUC mathematical model implementing a dynamic network in the post-contingency scenario is proposed as opposed to current industry practices of static network in short-term operations. The proposed model is tested and validated on the IEEE 24-bus system. The proposed model results in cost-effective implementation and leads to overall reduced cost, and congestion reduction in the post-contingency scenario.
提交历史
来自:Xingpeng Li[v1] 2020年1月6日 星期一 00:00:00 UTC