标题:Impact of High PV Penetration on the Inter-area Oscillations in the U.S. Eastern Interconnection
查看原文 PDF 中文 PDF (下批处理) EasyResearch 阅读摘要:This study explores the impact of high PV penetration on the inter-area oscillation modes of large-scale power grids. A series of dynamic models with various PV penetration levels are developed based on a detailed model representing the U.S. Eastern Interconnection (EI). Transient simulations are performed to investigate the change of inter-area oscillation modes with PV penetration. The impact of PV control strategies and parameter settings on inter-area oscillations is studied. This study finds that as PV increases, the damping of the dominant oscillation mode decreases monotonically. It is also observed that the mode shape varies with the PV control strategy and new oscillation modes may emerge under inappropriate parameter settings in PV plant controls.