标题:Numerical analysis of partial discharge ignition in H2 bubbles floating in dielectric oils, for High-Voltage Solid State Transformer applications

作者:Konstantinos Kourtzanidis, Panagiotis Dimitrakellis, Dimitrios Rakopoulos
查看论文《Numerical analysis of partial discharge ignition in H2 bubbles floating in dielectric oils, for High-Voltage Solid State Transformer applications》的 PDF
查看原文 PDF 中文 PDF (下批处理) EasyResearch 阅读
摘要:We report on a self-consistent numerical analysis campaign of partial discharge (PD) ignition in H2 bubbles floating in biobased dielectric oils. We investigate various configurations (bubble sizes, bubble position, existence of protrusion) on a cylinder-to-cylinder setup that emulates a specific SST module (from SSTAR Horizon Europe project) under transient overvoltage as well as in its design operational conditions (VRMS = 66 kV, AC excitation of 50 Hz). Our results on electrical characteristics and plasma dynamics leading to the PD ignition, indicate that under transient overvoltage and for mm size bubbles (diameter 1 -4.5 mm), the smaller the bubble the less the inception voltage, while the peak inception voltage is higher than 70 kV. The existence of metallic protrusion can affect the inception voltage of a remote floating bubble only slightly and when this is close to the sharp tip. The extreme scenario of a protrusion in contact (inside) a gas bubble severely affects the insulation properties and drops the PD inception voltage remarkably. The larger the bubble and the sharper the tip of the protrusion the lower the inception peak voltage, that can reach values well below 40 kV. On the contrary and under design operation, larger bubbles increase the severity and probability of PD events, leading to lower instantaneous inception voltages. Current pulses produced in bubbles can quickly transit to intense streamer discharges (which can also transit to catastrophic arcing) if the operational frequency is reduced and/or under transient, HF overvoltage.
评论: Submitted to IEEE Transactions on Dielectrics and Electrical Insulation
主题: 等离子体物理 (physics.plasm-ph); 计算物理 (physics.comp-ph)
引用方式: arXiv:2410.05927 [physics.plasm-ph]
  (或者 arXiv:2410.05927v1 [physics.plasm-ph] 对于此版本)
  https://doi.org/10.48550/arXiv.2410.05927

提交历史

来自:Konstantinos Kourtzanidis Dr
[v1] 2024年10月10日 星期四 00:00:00 UTC
全文链接:

访问论文:

  • 查看原文 PDF
  • 中文 PDF (下批处理)
  • EasyResearch 阅读
  • TeX 源文件
  • arXiv 原文页面
查看许可

当前浏览上下文:

physics.plasm-ph
< 上一篇   |   下一篇 >
最新 | 近期 | 2024-10
切换浏览方式为:
physics
physics.comp-ph

参考文献与引用

  • Google Scholar
  • Semantic Scholar

BibTeX 格式的引用

EasyXiv 是独立运营的中文预印本站点,与 arXiv 及康奈尔大学无隶属关系。 论文元数据与原文来自 arXiv.org,感谢 arXiv 提供开放获取服务。
关于 · 帮助 · 投稿指南 · 版权 · arXiv 原站