标题:Frequency-Dynamics-Aware Economic Dispatch with Optimal Grid-Forming Inverter Allocation and Reserved Power Headroom
查看原文 PDF 中文 PDF (下批处理) EasyResearch 阅读摘要:The high penetration of inverter-based resources (IBRs) reduces system inertia, leading to frequency stability concerns, especially during synchronous generator (SG) outages. To maintain frequency dynamics within secure limits while ensuring economic efficiency, frequency-constrained optimal power flow (FCOPF) is employed. However, existing studies either neglect the frequency support capability and allocation of grid-forming (GFM) IBRs or suffer from limited accuracy in representing frequency dynamics due to model simplifications. To address this issue, this paper proposes a deep learning (DL)-based FCOPF (DL-FCOPF) framework. A DL model is first developed as a predictor to accurately estimate frequency-related metrics: the required reserved headroom and allocation of GFM IBRs, the rate of change of frequency and frequency nadir. After being trained with data obtained from electromagnetic transient simulations, the DL model is reformulated and incorporated into FCOPF. Case studies conducted on two test systems demonstrate the effectiveness of the proposed approach. Compared with the traditional OPF and linear FCOPF benchmarks, the DL-FCOPF can optimally coordinate SGs and IBRs with minimum cost, achieving desired frequency response, within an acceptable computing time. Further-more, sensitivity analyses are conducted to identify the most suit-able structure and linearization approach of the DL-based frequency predictor.
提交历史
来自:Fan Jiang[v1] 2025年12月1日 星期一 15:47:28 UTC