电气工程与系统科学 > 系统与控制
[提交于 2026年2月1日]
标题:Mitigating Data Centers Load Risks and Enabling Grid Support Functions through Grid-Forming Control
查看中文 PDF 查看原文 PDF EasyResearch 阅读摘要:The rapid growth of hyperscale data centers driven by Large Language Models and Artificial Intelligence workloads has introduced new challenges for power systems. These facilities experience abrupt power variations during model training and check-point-saving events, causing voltage deviations and frequency disturbances. Moreover, they operate as passive loads that draw power without offering any grid support. This paper presents an integrated architecture that combines Battery Energy Storage Systems (BESSs) within data centers using Grid-Forming inverters to provide active grid-support functions. Simulation results through MATLAB/Simulink demonstrate accurate power reference tracking under dynamic loading, with eight coordinated BESS units supplying instantaneous power during training and saving conditions. Under single-phase voltage depression near the data center bus, the BESS delivered reactive power support similar to a Static Synchronous Compensator. During grid disconnection, seamless islanded operation was achieved with stable voltage, frequency, and continuous power delivery at the data center bus.
提交历史
来自:Yousef Abudyak[v1] 2026年2月1日 星期日 04:43:23 UTC (2,248 KB)