标题:Hosting Capacity Assessment of Data Centers with Voltage Ride-Through Capability in Power Systems

作者:Pengyu Ren, Wei Sun, Fei Teng
查看论文《Hosting Capacity Assessment of Data Centers with Voltage Ride-Through Capability in Power Systems》的 PDF
查看原文 PDF 中文 PDF (下批处理) EasyResearch 阅读
摘要:Large data centers are emerging as concentrated, power-electronic grid loads whose abrupt disconnection or transfer to on-site backup supply during voltage disturbances can remove large demand from the power system, and may create a system-level stability problem. Their interconnection feasibility therefore depends not only on steady-state thermal and voltage limits, but also on whether internal power-conditioning systems can maintain IT service while limiting customer-initiated load reduction. This paper presents a voltage ride-through (VRT)-aware data center and grid co-planning framework that couples transmission-level fault simulation with an internal data center ride-through model. Python-based dynamic simulations generate point-of-interconnection (POI) voltage trajectories under selected network faults, and the resulting waveforms drive an internal model incorporating IT and cooling-load dynamics, DC-link, Uninterruptible Power Supply (UPS) response, and converter apparent power limits. The IEEE 118-bus case study shows that internal VRT capability can become a binding interconnection constraint: steady-state planning alone can overestimate feasible data center capacity, whereas increased UPS converter headroom progressively restores hosting capacity. Under the reduced-order response models studied, the grid-forming mode provides greater ride-through margin than the current-limited grid-following mode under the same network fault conditions. The results further show that VRT constraints can materially change both the total hosting capacity of data centers and its spatial allocation across candidate interconnection buses.
主题: 系统与控制 (eess.SY); 系统与控制 (cs.SY)
引用方式: arXiv:2609.03030 [eess.SY]
  (或者 arXiv:2609.03030v1 [eess.SY] 对于此版本)
  https://doi.org/10.48550/arXiv.2609.03030

提交历史

来自:Pengyu Ren
[v1] 2026年9月2日 星期三 18:04:05 UTC
全文链接:

访问论文:

  • 查看原文 PDF
  • 中文 PDF (下批处理)
  • EasyResearch 阅读
  • TeX 源文件
  • arXiv 原文页面
查看许可

当前浏览上下文:

eess.SY
< 上一篇   |   下一篇 >
最新 | 近期 | 2026-09
切换浏览方式为:
eess
cs.SY

参考文献与引用

  • Google Scholar
  • Semantic Scholar

BibTeX 格式的引用

EasyXiv 是独立运营的中文预印本站点,与 arXiv 及康奈尔大学无隶属关系。 论文元数据与原文来自 arXiv.org,感谢 arXiv 提供开放获取服务。
关于 · 帮助 · 投稿指南 · 版权 · arXiv 原站