标题:Control-Layer Interpretation of Reactive Power Recovery Limits in EMT-RMS Model Benchmarking of Inverter-Based Resources

作者:Dileep Cheerla, Amirthagunaraj Yogarathnam, Divya Jain, Satish Natti
查看论文《Control-Layer Interpretation of Reactive Power Recovery Limits in EMT-RMS Model Benchmarking of Inverter-Based Resources》的 PDF
查看原文 PDF 中文 PDF (下批处理) EasyResearch 阅读
摘要:EMT--RMS benchmarking is widely used to verify cross-platform consistency of inverter-based resource (IBR) dynamic models. This paper examines a 200 MW anonymized IBR represented in PSCAD and PSS/E. The EMT model separates inverter electrical capability from a plant-level power plant controller (PPC) recovery target, whereas the RMS model represents these functions through REECC and REPCA parameters. Directly assigning the PPC target of $\pm 0.2764$ pu to REPCA hard reactive limits is initialization-inconsistent at the original lagging operating point because the initial reactive command is 0.396273 pu. A second, near-unity-power-factor operating point initializes successfully with the same diagnostic limit, demonstrating that the conflict is operating-point dependent. Using the non-conflicting capability mapping removes the original hard-limit conflict, but the benchmark still shows 18.5--30.2 MVAr post-event POI reactive-power differences from PSCAD. A one-at-a-time REPCA $K_c$ sensitivity under matched benchmark initial conditions further shows that RMS recovery is parameter- and limit-dependent: at $K_c=0.05$ and 0.10 the aggregate machine reactive output reaches the configured capability bounds, while $K_c=0.15$ moves VDOWN, VUP, and HVRT off those bounds and changes their settled POI reactive power by 8.94, 18.00, and 3.17 MVAr, respectively. Machine-to-POI accounting further shows why machine-side saturation need not reproduce the POI-level PPC recovery magnitude. The results distinguish initialization feasibility from recovery equivalence and provide a control-layer diagnostic workflow beyond waveform comparison.
评论: Accepted for presentation at IEEE PES Grid Edge Technologies 2027, April 19-22, 2027, Salt Lake City, Utah, USA.5 pages, 3 figures, 6 tables
主题: 系统与控制 (eess.SY); 系统与控制 (cs.SY)
引用方式: arXiv:2610.41221 [eess.SY]
  (或者 arXiv:2610.41221v1 [eess.SY] 对于此版本)
  https://doi.org/10.48550/arXiv.2610.41221

提交历史

来自:Dileep Cheerla
[v1] 2026年10月30日 星期五 03:59:22 UTC (1,178 KB)
全文链接:

访问论文:

  • 查看原文 PDF
  • 中文 PDF (下批处理)
  • EasyResearch 阅读
  • TeX 源文件
  • arXiv 原文页面
查看许可

当前浏览上下文:

eess.SY
< 上一篇   |   下一篇 >
最新 | 近期 | 2026-11
切换浏览方式为:
eess
cs.SY

参考文献与引用

  • Google Scholar
  • Semantic Scholar

BibTeX 格式的引用

EasyXiv 是独立运营的中文预印本站点,与 arXiv 及康奈尔大学无隶属关系。 论文元数据与原文来自 arXiv.org,感谢 arXiv 提供开放获取服务。
关于 · 帮助 · 投稿指南 · 版权 · arXiv 原站