跳到正文
EasyXiv 检索
投稿 关于 登录

按回车检索 · 直接输入编号(如 1706.03762)可跳转到论文

电气工程与系统科学 > 系统与控制

arXiv:2611.33656 (eess)
[提交于 2026年11月25日]

标题:Online Identification Can Replace a Floor-Plan Prior on Unseen Buildings

作者:Elias T.-H. Shieh, Chun Fu
查看论文《Online Identification Can Replace a Floor-Plan Prior on Unseen Buildings》的 PDF
查看原文 PDF 中文 PDF (下批处理) EasyResearch 阅读
摘要:The Smart Buildings Challenge asks for one HVAC control policy that runs office buildings and weather it has never seen, from the building's metadata and sensor streams alone. Our controller sees no data from the target building before it runs and is not tuned per building; its few global constants were set on development scenarios. Each zone has a first-order grey-box model that starts from coefficients computed from the floor plan and is updated online by recursive least squares, and a planner and a closed-form mapping turn the models into plant commands. On two sets of buildings and weather that we generated, a validation set and a stress set with real-year weather, it scores 0.145 and 0.159 times the starter kit's PID baseline, and 0.095 times on a holdout built after all versions were fixed and scored once. It improves on every building, also against our two implementations of ASHRAE Guideline 36: per set it scores 0.60 to 0.71 times a basic version and 0.83 to 0.96 times one partly tuned on the public leaderboard, which wins one of 54 scenarios; with a 5 {\deg}C frost target for empty zones on both, the margin over the tuned version shrinks to 1.4% on the stress set, where one of six buildings is 0.2% worse. In an ablation on a reduced-order model, removing both the floor-plan prior and online identification costs 28%, 20% and 42% on the validation, stress and holdout sets, far more than the two effects combined: either source of building-specific information recovers most of what is lost without both. On one office floor in a second simulator, BOPTEST, this does not carry over: with identification on, the two priors give similar results, but the floor-plan prior alone, with constants fitted on the competition's simulator, is the least stable arm. These simulation results motivate testing floor-plan-initialised adaptive control in buildings that have drawings but no operating data.
评论: Smart Buildings Competition Track, NeurIPS 2026. First place, Round One paper prize. 8 pages main text, 21 pages in total, 8 figures, 5 tables
主题: 系统与控制 (eess.SY); 机器学习 (cs.LG); 系统与控制 (cs.SY)
引用方式: arXiv:2611.33656 [eess.SY]
  (或者 arXiv:2611.33656v1 [eess.SY] 对于此版本)
  https://doi.org/10.48550/arXiv.2611.33656

提交历史

来自:Chun Fu
[v1] 2026年11月25日 星期三 02:23:50 UTC (878 KB)
全文链接:

访问论文:

  • 查看原文 PDF
  • 中文 PDF (下批处理)
  • EasyResearch 阅读
  • TeX 源文件
  • arXiv 原文页面
查看许可

当前浏览上下文:

eess.SY
< 上一篇   |   下一篇 >
最新 | 近期 | 2026-11
切换浏览方式为:
eess
cs.LG
cs.SY

参考文献与引用

  • Google Scholar
  • Semantic Scholar

BibTeX 格式的引用

EasyXiv 是独立运营的中文预印本站点,与 arXiv 及康奈尔大学无隶属关系。 论文元数据与原文来自 arXiv.org,感谢 arXiv 提供开放获取服务。
关于 · 帮助 · 投稿指南 · 版权 · arXiv 原站