电气工程与系统科学 > 系统与控制
[提交于 2026年11月25日]
标题:Grey-Box Experimental Identification of Reduced-Order Models for Grid-Forming Converters
查看原文 PDF 中文 PDF (下批处理) EasyResearch 阅读摘要:This paper proposes a grey-box system identification for identifying and validating reduced-order models (ROMs) of grid-forming (GFM) converters. Three reduced-order modeling techniques are compared within a common identification procedure: singular perturbation with frequency cutoff and participation factors (SP-PF), singular perturbation with energy residuals (SP-Energy), and balanced truncation (BT). Testing is on experimental data with real-life components. Results show that BT achieves the highest time-domain fit, followed by SP-Energy and SP-PF; SP-Energy better preserves key properties of the identified full-order model; BT places the dominant mode closest to the stability boundary and exhibits the highest sensitivity to parameter variations; SP-Energy outperforms SP-PF in both fit quality and consistency of modal preservation. Findings suggest that the model with the best time-domain fit does not always provide the most reliable representation of the modal properties for small-signal stability, with SP-Energy offering the best compromise between accuracy, physical interpretability, and modal preservation for the considered case study.
提交历史
来自:Marcelo Cardenas[v1] 2026年11月25日 星期三 15:34:37 UTC (3,691 KB)